Single phase surge surppression transformer
|
With
the occurrence of lightning, the induced electric charge on the power
lines produced by |
@
| Surge Suppression Transformer (Single-Phase) | ||
| Image | Specifications | |
![]() |
Primary
Voltage |
AC 100V/200V/220V |
|
Secondary
Voltage |
AC 100V/200V/220V | |
|
Frequency
|
50 / 60Hz | |
|
Voltage
Variation |
0.2 to 0.5kVA
: below 7% 1.0 to 3.0kVA : below 5% |
|
|
Voltage
Deviation |
within +/- 3% | |
|
Withstanding
Voltage |
AC10kV,
1 minute duration between Primary and Secondary; between Primary and Ground AC3kV, 1 minute duration between Secondary and Ground |
|
|
Impulse
|
1.2/50 microseconds
30kV between Primary and Secondary; between Primary and Ground |
|
|
Insulation
Resistance |
with DC500V: 100 Mega Ohms and above | |
|
Surge
Attenuation
(Balanced) |
below -40dB | |
|
Temperature
Rise
|
below 75 degrees centigrade | |
|
Insulation
Class
|
Class B | |
| Surge Suppression Transformer (Single-Phase) Dimensions | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||
![]()
|
@