Three phase surge surppression transformer
|
With
the occurrence of lightning, the induced electric charge on the power
lines produced by electrostatic |
@
| Surge Suppression Transformer (3-Phase) | ||
| Image | Specifications | |
![]() |
Primary
Voltage
|
200V (Delta Connection) |
|
Secondary
Voltage |
200V (Delta Connection) | |
|
Frequency
|
50 / 60Hz | |
|
Voltage
Variation |
below 5% | |
|
Voltage
Deviation |
within +/- 3% | |
|
Withstanding
Voltage |
AC 10kV, 1minute duration AC3kV, 1minute duration |
|
|
Impulse
|
1.2/50
microseconds,@30kV between primary and secondary; between primary and ground |
|
|
Insulation
Resistance
|
with DC500V: 100 Mega Ohms and above. | |
|
Surge
Attenuation (Balanced)
|
below -40dB | |
|
Temperature
Rise
|
below 75 degrees centigrade | |
|
Insulation
Class
|
Class B | |